Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T10BU00020
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2011 | FIRE - ALARM FINAL | Approved | Approved 3/2/11 | |
02/28/2011 | FIRE - ALARM FINAL | Cancelled | A new contractor called and asked if we knew anything about this permit and why it is still open, his company is tiring to start a new project but city will not give a new permit until old ones are closed out. | |
01/14/2010 | FIRE - ALARM FINAL | Denied | Not approved 1/14/10. 1.) Need to replace the batteries for the main Fire Alarm Panel from 18 AH to 33 AH batteries, as indicated on the plans. 2.) Need to indicate the date when the batteries were installed . If unable to present documentation of DATES. the batteries must be replaced. 3.)Need a breaker lock for the breaker supplting the Fire Alarm Panel. 4.) Per Fire Code, 2 dedicated phone lines to central monitoring station are required for the alarm system. Only one is provided. 5.) All appliances have been tested and approved. |