Permit: T09PL02197

Parcel: 126152010


Addresses:

4424 E 15TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/25/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
01/05/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HAVE INSTALLER ON SITE TO PROVIDE A MEANS FOR GAS PIPING TEST, SOAP TEST CAN BE USED
2) THE FURNACE VENT IS NOT PROPERLY CONNECTED AND NEEDS TO BE REPAIRED IMMEDIATELY WITH DBL WALL VENT PIPING PROPERLY INSTALLED FROM SINGLE TO DBL WALL CONENCTION, NO TAPE AT JOINTS AND DBL WALL TO TERMINATION AT VENT CAP
3) PETITION OF APPEAL FOR ALTERNATE FORM OF TEMPERTURE AND PRESSURE RELIEF LEFT ON STIE TO BE FILLED OUT AND SIGNED BY OWNER FOR PICK UP AT REINSPECTION
4) CUT TEMPERATURE AND PRESSURE RELIEF DRAIN PIPE 1" ABOVE PAN