Permit: T09PL02192

Parcel: 121020330


Addresses:

5425 E WAVERLY ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T09PL02192

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/05/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
01/04/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECURE WATER HEATER VENT CONNECTOR WITH 3 GALV SHEET METAL SCREWS IN EACH JOINT
2) REMOVE CHECK VALVE ON CW SUPPLY OR INSTALL A METHOD OF EXPANSION CONTROL FOR CLOSED LOOP SYSTEM
3) REMOVE BLACK COUPLING ON WATER HEATER DRAIN VALVE
4) SEDIMENT TRAPS REQUIRED
5) TEST ENTIRE GAS SYSTEM (OPEN HOUSE SOVF)
6) SECURE TRACER WIRE TO RISER ABOVE GRADE
12/30/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXPOSE PIPING COVERED WITHOUT INSPECTION
2) YELLOW TRACER WIRE REQUIRED WITH NON METALLIC PIPING. 1" REQUIRED 18" OF COVER REQUIRED. CONNECT NEW YARD LINE TO HOUSE AND PROVIDE A TEST ON THE ENTIRE SYSTEM
3) INSTALL LISTED GAS VALVES AND FLEXES
4) CHECK T & P RELIEF VALVE FOR PROPER OPERATION
5) SECURE VENT CONNECTORS WITH SCREWS
6) COMBUSTION AIR OPENINGS
7) A CLOSED LOOP SYSTEM WITH A CHECK VALVE REQUIRES AN EXPANSION TANK
8) SOLAR SYSTEMS AND NEW WHS REQUIRES PERMITS
12/29/2009 PLUMBING - FINAL Cancelled CANCELLED PER HOMEOWNER MAX #360-4882
12/29/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*