Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09PL02192
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 01/04/2010 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE WATER HEATER VENT CONNECTOR WITH 3 GALV SHEET METAL SCREWS IN EACH JOINT 2) REMOVE CHECK VALVE ON CW SUPPLY OR INSTALL A METHOD OF EXPANSION CONTROL FOR CLOSED LOOP SYSTEM 3) REMOVE BLACK COUPLING ON WATER HEATER DRAIN VALVE 4) SEDIMENT TRAPS REQUIRED 5) TEST ENTIRE GAS SYSTEM (OPEN HOUSE SOVF) 6) SECURE TRACER WIRE TO RISER ABOVE GRADE |
|
| 12/30/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSE PIPING COVERED WITHOUT INSPECTION 2) YELLOW TRACER WIRE REQUIRED WITH NON METALLIC PIPING. 1" REQUIRED 18" OF COVER REQUIRED. CONNECT NEW YARD LINE TO HOUSE AND PROVIDE A TEST ON THE ENTIRE SYSTEM 3) INSTALL LISTED GAS VALVES AND FLEXES 4) CHECK T & P RELIEF VALVE FOR PROPER OPERATION 5) SECURE VENT CONNECTORS WITH SCREWS 6) COMBUSTION AIR OPENINGS 7) A CLOSED LOOP SYSTEM WITH A CHECK VALVE REQUIRES AN EXPANSION TANK 8) SOLAR SYSTEMS AND NEW WHS REQUIRES PERMITS |
|
| 12/29/2009 | PLUMBING - FINAL | Cancelled | CANCELLED PER HOMEOWNER MAX #360-4882 | |
| 12/29/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |