Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2010 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 12/30/2009 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 1. BONDING TO BE DONE TO BUILDING GAS PIPING THAT IS NOT COATED PIPING. THE INNER LINER OF THE DOUBLE WALL VENT PIPE AT THE CONNECTION TO THE SINGLE WALL VENT PIPE IS BROKEN LOOSE AND THIS CONNECTION POINT MUST BE CONNECTED PROPERLY PER NOT #1 ABOVE. 2. CUT THE T&P RELIEF DRAIN PIPE 1" ABOVE TOP LIP OF PAN PER NOTE #2 ABOVE. 3. CONTRACTOR TO PAY REINSPECTION FEE & RECALL FOR INSPECTION PRESSURE TEST OK, OK TO BURY YARD PIPING |
|
| 12/24/2009 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* |