Permit: T09PL02062

Parcel: 133421090

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/30/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CALLED FOR OTHER ACTIVITY
12/24/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE THE TEE ON RELIEF DRAIN, INSTALL A 90 TO PROVIDE A 1" AIR GAP
2) PROVIDE THE MECHANICAL PERMIT REQUIRED, AS NOTED
3) CONTINUED DENIED INSPECTIONS WILL RESULT IN REINSPECTION FEES
12/18/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE PROPERLY JOINED CPVC SOLVENT WELDED CONNECTIONS, WITH COMPLETE MAKE UP OF FITTINGS. USPE UPC CODE APPROVED SOLVENT CEMENT (GLUE (UPC)
2) PROVIDE AN AIR GAP BETWEEN RELIEF DRAIN AND INDIRECT WASTE RECEPTOR
3) CHECK AND REPLACE TEMPERATURE RELIEF VALVES AS NEEDED-SEE WARNING TAG ON VALVE
4) SECURE VENT CONNECTOR TO DRAFT COLLAR WITH SCREWS
12/17/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) 14 13.5 13.8 13.8 13.7
2) 3 ROOF TOP UNITS HAVE BEEN REPLACED WITHOUT INSPECTION AND HAVE OBVIOUS CODE VIOLATIONS
3) PLEASE OBTAIN PERMITS AND SCHEDULE AN INSPECTION THEN RECALL IN THIS PERMIT FOR FINAL APPROVAL
4) AT NEW WH'S PROVIDE 3 X 4 SINGLE WALL INCREASERS AND SECURE WITH SCREWS BUT NO TAPE
5) PIPE T & P'S WITH MATERIAL APPROVED FOR HW AND DO NOT USE FLEXIABLE CONNECTORS, ALSO PROVIDE AIR GAPS-OK TO BURY
6) GAS CLEARANCE FOR ALL EXCEPT WHS
12/15/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) IDENTIFY ROOF TOP UNITS, CORRECT LEAKS AND SUPPORT ALL PIPING
2) COMPLETE PIPING TO UNIT
3) PROVIDE PERMITS FOR NEW ROOF TOP UNITS (2) AND NEW WATER HEATERS (2)
4) WRAP ALL TOOL MARKS
5) TERMINATE, T & P'S, CORRECT VENTS INSTALL SEDIMENT TRAPS