Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2009 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/09/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL EXTERIOR WALL PENETRATIONS 2) SEPERATE AND SECURE TUBING ABOVE SINKS 3) SEPERATE AND SECURE TUBING ABOVE LIVING ROOM-KIT. 4) INSTALL ADDITIONAL ISOLATORS WHERE PASSING THRU STUDS. PLASTIC TOUCHING GANG NAILER 5) SECURE AND ISOLATE AT EXHAUST FAN 6) SECURE AND ISOLATE ABOVE CEILING IN GARAGE 7) CAP AT SERVICE IN WALL 8) HW ON WRONG SIDE AT LAV |
|
| 12/08/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) WORK NOT COMPLETE 2) PROVIDE 1" PIPING OUTSIDE OF WALL AT EXISTING SOFTNER LOCATION |