Date Description Inspector Results Comments
12/09/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
12/08/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE SUPPORT ON ALL GAS PIPING
2) MOVE BONDING TO COLD WATER SIDE
3) PROVIDE 3 SCREW ON ALL JOINTS IN FLOW VENT FOR WATER HEATER
4) PROVIDE COMBUSTION AIR FOR WATER HEATER ROOM
5) PROVIDE 1" CLEARANCE AROUND FLUE VENT THRU ROOF
6) UNDERGROUND TEST OK