Permit: T09PL01969

Parcel: 11306045A


Addresses:

3390 N CAMPBELL AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/14/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
12/11/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SEE NOTE #2 FROM 12/08/09
12/08/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) YARD LINE OK TO COVER AFTER SECURING TRACER WIRE TO PIPE AT 8' ON CENTER PER STATE LAW, AND USING A WEATHER RESISTANT WIRE NUT
2) RP REQUIRED PER TUCSON WATER
3) INSTALL HOSE BIB VACUUM BREAKERS
4) PROVIDE CODE APPROVED BACKFLOW PROTECTION AT IRRIGATION SUPPLY
5) PROVIDE A PRESSURE GAUGE TO CHECK PRESSURE