Permit: T09PL01882

Parcel: 124060970


Addresses:

1211 E 9TH ST #04

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/13/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
1) GAS CARD AT METER
11/12/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSPECTORS NEED ACCESS TO ALL UNITS AT TIME OF REINSPECTION
2) NEWER WATER HEATERS REQUIRE CORRECT VENT PIPING AND VENT CAPS
UNIT 4:
1) PROVIDE A FUNCTION GAS TEST GAUGE IN 1/10 POUND INCREMENTS WITH TEST HOLDING MINIMUM 10 PSI FOR 15 MINUTES AT TIME OF INSPECTION
UNIT 9:
1) NO ACCESS FOR INSPECTION
UNIT 10:
1) NO ACCESS FOR INSPECTION
2) PROVIDE A FUNCTION GAS TEST GAUGE IN 1/10 POUND INCREMENTS WITH TEST HOLDING MINIMUM 10 PSI FOR 15 MINUTES
3) LIST NOT COMPLETE