Permit: T09PL01846

Parcel: 127031100


Addresses:

5731 E 2ND ST

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/09/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A 10 PSI TEST (CORRECT LEAK)
2) REMOVE OR CORRECT UNSUPPORTED BRANCH TO ABANDON WATER HEATER
3) CORRECT UNPERMITTED WATER HEATER IN MAIN HOUSE
4) PIPE T & P DRAIN BY GRAVITY TO APPROVED LOCATION
5) (DUAL INLET WASHER BOX) WITH AIR GAP
6) CHECK T & P VALVE FOR OPERATION
7) B-VENT INSTALLED UPSIDE DOWN
8) SUPPORT PIPING AT WATER HEATER/FURNACE LOCATION