Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2009 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1) 11 PSI TEST OK 2) LEFT GAS CARD |
|