Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2009 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1) COMPLETE WALL FURNACE 2) RUN T & P TO DAYLIGHT 6" TO 24" OF GROUND 3) COMPLETE FLUE VENT AT WATER HEATER, TYPE B CAP AND PROVIDE SEDIMENT TRAP 4) PROVIDE COMBUSTION AIR FOR WATER HEATER 5) CALL BACK FOR FINAL FOR GAS CARD |