Permit: T09PL01725

Parcel: 133520390


Addresses:

101 N NIGHTFALL AV


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T09PL01725

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/06/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
10/30/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) I WILL NOT ACCEPT OLD SUN BURNT PVC, COMPARE TO THE WHITE FITTINGS
2) UPC DOES NOT ALLOW PVC TO BE EXPOSED TO SUN LIGHT
10/23/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
FITTINGS MAY NOT BE STRAINED, ALSO PROVIDE MINIMUM 12" AT SIDE WALK
OK TO COVER ALL BUT AT SIDEWALK AFTER SECURING TRACOR WIRE TO PIPE AS REQUIRED.
10/22/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) INTERIOR PIPING OK
2) OK TO PATCH HOLES
3) NEED TO SEE EXTERIOR YARD WATER LINE