Permit: T09PL01706

Parcel: 116125660

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/23/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
1) OK FOR GAS
10/20/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) 1211.1.1 2006 UPC UNDERGROUND PIPING SYSTEMS SHALL BE INSTALLED WITH SUFFICIENT CLEARANCE FROM ANY OTHER UNDERGROUND STRUCTURE
2) 1211.1.2 UNDERGROUND PIPING SYSTEMS SHALL BE INSTALLED WITH A MINIMUM OF 18" OF COVER. WHERE EXTERNAL DAMAGE TO THE PIPE IS NOT LIKELY TO RESULT, THE MINIMUM COVER SHALL BE 12"
2) SEAL EXTERNAL WALL PENETRATION
3) THE SHUT OFF VALVE FOR THE LOG LIGHTER MAY NOT BE IN THE HEARTH