Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2009 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 10/20/2009 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 10/16/2009 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) TEST TO HOLD 10 PSI MIN FOR 15 MINUTES 2) PROVIDE APPROVEDF 90 DEGREE (MALLABLE IRON) NO CAST IRON 3) PROVIDE PIPE PRIMER THEN TAPE ALL UNDERGROUND FITTINGS AND TOOL MARKS TO ACHIEVE 40 MIL WRAP 4) PROVIDE ROOF FLASHING AT ROOF PENETRATION AND MAKE IT WEATHER TIGHT 5) COMPLETE GAS PIPING TO WATER HEATER/FURNACE APPROVED GAS SHUT OFF VAVLES AND SECURE THIS PIPING IN CLOSET 6) PROVIDE BONDING OF GAS SYSTEM 7) RESEAL RETURN AIR PLENIUM |