Date Description Inspector Results Comments
06/09/2010 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
06/07/2010 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) PROVIDE A 10 PSI AIR TEST ON SYSTEM
2) REPAIR ALL LEAKS BEFORE CALLING FOR INSPECTION
06/03/2010 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) PROVIDE A 10 PSI AIR TEST ON SYSTEM
2) PROVIDE AN OPERATIONAL T & P RELIEF VALVE
3) SECURE VENT TO WH DRAFT COLLAR
4) BOND TO UN-COATED PIPING
04/01/2010 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) PROVIDE FACTORY COATED PIPING FOR UNDERGROUND GAS PIPING
2) PROVIDE TRIMMER AND TAPE ON ALL FITTING UNDERGROUND
3) UNION CANNOT BE USED UNDERGROUND
4) PROVIDE SEDIMENT TRAP AT WATER HEATER
5) PROVIDE TYPE B FLUE CAP AT WATER HATER
6) HAVE DRAWINGS AND PERMIT ON SITE
7) LIST MAY NOT BE COMPLETE