Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2009 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 10/09/2009 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) 1:12 PM NO ANSWER AT DOOR AND NO ACCESS |
|
| 10/08/2009 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TEST TO BE ON ENTIRE GAS SYSTEM AT TIME OF INSPECTION HOLDING WITH NO LOSS OF PRESSURE FOR 15 MINUTES 2) PROVIDE APPROVED GAS SHUT OFF VALVES AT ALL LOCATIONS 3) TEMPERATURE AND PRESSURE RELIEF TO BE FUNCTIONAL AND GRAVITY DRAIN TO DAY LIGHT OR INSTALLED PER PETITION OF APPEAL LEFT ON SITE 4) PROVIDE BONDING OF BLDG GAS PIPING |