Permit: T09PL01569

Parcel: 128141120


Addresses:

522 S MAGNOLIA AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/05/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
1) GAS CARD AT METER
09/28/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT ROOF TOP PIPING AND SECURE AT CORRECT INTERVALS
2) PROVIDE APPROVED GAS SHUT OFF VALVE AT FURNACE AND SUPORT & SECURE GAS PIPING AT FURNACE
3) PROVIDE UPPER COMBUSTION AIR FOR WATER HEATER
4) PROVIDE BONDING OF GAS SYSTEM
5) PROVIDE 1" MINIMUM CLEARANCE FROM COMBUSTIBLES FOR DBL WALL VENT FROM WATER HEATER
6) PROVIDE FASTENERS FOR ALL VENT PIPING