Permit: T09PL01520

Parcel: 10601148A


Addresses:

3709 N LOS ALTOS AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/25/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS MADE OK
2) OK FOR GAS
09/22/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) GAS PIPING MAY NOT RUN ON THE ROOF, MUST BE KEPT A MINIMUM OF 1 1/2"-3 1/2" ABOVE THE ROOF
2) ALL PENETRATIONS REQUIRE FLASHINGS
3) AT WATER HEATER:
A) REQUIRE AN APPROVED VALVE AT COLD WATER INLET
B) REQUIRE APPROVED MATERIALS FOR T & P RELIEF DRAIN
C) T & P RELIEF DRAIN TO TERMINATE AT EXTERIOR OF BLDG WITH NO THREADS
4) USE APPROVED MATERIAL FOR WATER HEATER VENT ("B" VENT OUTSIDE) AND MAINTAIN 1" CLEARANCE FOR COMBUSTIBLES