Permit: T09PL01469

Parcel: 10709008A


Addresses:

2637 N ORACLE RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T09PL01469

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/02/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
NEED ISOLATION VALVE FOR APPLIANCES AND APPROVED PIPE SUPPORTS AT OXP TANKS
MANUFACTURE REQUIREDS THAT TEMPERATURE + PRESSURE RELIEF VALVE GET TESTED ANNUALLY, AND REPLACED OF NECCESARY.
WHS ARE OLD. ALL BASIC SAFETY REQUIREMENTS HAVE BEEN CORRECTED.
PROVIDE PERMITS AS NEEDED FOR FURTURE "REPLACEMENTS"
09/17/2009 PLUMBING - FINAL Not ready for Inspection THERE ARE SEVERAL WH'S ON THIS SITE.
PROVIDE CORRECT SUPPORTS AT ROOF
PROVIDE CORRECT VENT TERMINATION (TYPE B)
PROVIDE FLASHINGS
PROVIDE SEPARATE GAS SOV'S?
REMOVE CHOCK VALVE AT WH OR INSTALL EXPANSION DEVICE AT WH
THIS IS A CLOSED LOOP SYSTEM AND A METHOD TO CONTROL EXPANSION OF HW SYSTEM IS REQUIRED
(WH'S #4) PIPE T&P TO EXTERIOR W/APPROVED MATERIALS.
PROVIDE CLEARANCE AT VENT PENATRATIONS
SECURE SINGLE WALL W/SCREWS.
B BENT TERMINATION IS 1' ASV ROOF IF NO AIR INLET