Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/11/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CALL GASRY IF ? ACCESS 2 GATES INTO BACKYARD 2) 20 PSI TEST ON 30 PSIT GAUGE, OK IF STILL HOLDING AT TIME OF NEXT INSPECTION 3) TYPE B VENT REQUIRES 1" OF CLEARANCE FROM WOOD 4) SECURE ALL JOINTS OF VENT CONNECTOR WITH GALVANIZED SCREWS 5) T & P SHALL TERMINATE 6"-24" ABOVE GRADE AND WITHOUT THREADS 6) WATER TO HEATER SHALL BE ON TO CHECK T & P OPERATION 7) PROVIDE WEATHER RESISTANT SUPPORTS ON ROOF 8) FLEX TO FURNACE IS UNDERSIZED. IT IS YOUR RESPONSIBILITY TO PROVIDE A PERMIT FOR UNLAWFULLY INSTALLED ROOF TOP FURNACE |
|
| 08/31/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) 1/2" PIPING TO NEW ROOF TOP FURNACE APPEARS TO BE UNDERSIZED 2) PROVIDE ACCESS (LADDER) TO INSPECT PIPING ABOVE ROOF 3) PROVIDE A PERMIT FOR NEW ROOF TOP FURNACE. WILL NEED WATER HEATER INSTALLED WITH PROPER VENTING AND CLEARANCES FOR FINAL APPROVAL. ALSO T & P TERMINATION 4) NOTE: WATER LINES TO LAUNDRY INSTALLED WITHOUT INSPECTION 5) PVC WITH IMPROPER CONNECTIONS 6) ALL WORK REQUIRES PERMITS |