Permit: T09PL01439

Parcel: 110111060


Addresses:

4942 E GLENN ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/22/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
09/11/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CALL GASRY IF ? ACCESS 2 GATES INTO BACKYARD
2) 20 PSI TEST ON 30 PSIT GAUGE, OK IF STILL HOLDING AT TIME OF NEXT INSPECTION
3) TYPE B VENT REQUIRES 1" OF CLEARANCE FROM WOOD
4) SECURE ALL JOINTS OF VENT CONNECTOR WITH GALVANIZED SCREWS
5) T & P SHALL TERMINATE 6"-24" ABOVE GRADE AND WITHOUT THREADS
6) WATER TO HEATER SHALL BE ON TO CHECK T & P OPERATION
7) PROVIDE WEATHER RESISTANT SUPPORTS ON ROOF
8) FLEX TO FURNACE IS UNDERSIZED. IT IS YOUR RESPONSIBILITY TO PROVIDE A PERMIT FOR UNLAWFULLY INSTALLED ROOF TOP FURNACE
08/31/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) 1/2" PIPING TO NEW ROOF TOP FURNACE APPEARS TO BE UNDERSIZED
2) PROVIDE ACCESS (LADDER) TO INSPECT PIPING ABOVE ROOF
3) PROVIDE A PERMIT FOR NEW ROOF TOP FURNACE. WILL NEED WATER HEATER INSTALLED WITH PROPER VENTING AND CLEARANCES FOR FINAL APPROVAL. ALSO T & P TERMINATION
4) NOTE: WATER LINES TO LAUNDRY INSTALLED WITHOUT INSPECTION
5) PVC WITH IMPROPER CONNECTIONS
6) ALL WORK REQUIRES PERMITS