Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2009 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :* 1) SEWER INSTALLED OK 2) OK TO COVER |
|
| 12/04/2009 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE UNIFORM SLOPE SO AS TO PROVIDE 12" OF COVER ABOVE ALL PIPING 2) SHADE BOTTOM AND SIDES OF PIPING 3) THREADED FE FITTINGS MAY NOT BE CONCEALED, USE SOLVENT WELD TEST WYE OR TEST THRU PROP LINE CLEANOUT 4) IS FUTURE BRANCH SHOW ON PLAN ? |
|
| 09/17/2009 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection :* | |
| 09/17/2009 | PLUMBING - SEWER HCS CONNECT | Partial Approval |