Permit: T09PL01430

Parcel: 131110700


Addresses:

5617 E 31ST ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/28/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
08/27/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CENTER THE WATER HEATER DRAFT HOOD ON OUTLET OF WATER HEATER AND PROVIDE 1" CLEARANCE FROM COMBUSTIBLES (WOOD) AT CEILING OF DBL WALL VENT PIPING OF WATER HEATER. DRAFT HOOD NEEDS TO DROP INTO TABS THAT SECURE IT TO WATER HEATER
2) PROVIDE BONDING OF BLDG GAS PIPING SYSTEM
3) REATTACH BLDG GROUND WIRE TO WATER SERVICE