Permit: T09PL01426

Parcel: 131111790


Addresses:

5801 E 31ST ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/31/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
08/27/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TEST SHALL BE ON ENTIRE GAS SYSTEM HOLDING MINIMUM 10 PSI FOR 15 MINUTES UPON INSPECTION ARRIVAL
2) PROVIDE BONDING OF BLDG GAS PIPING
3) PIPING UNDERGROUND TO BE PRIMED THEN TAPED TO ACHIEVE 40 MIC WRAP
4) PIPING IN GROUND TO BE SUPPORTED ON FIRM BEDDING IN IT'S ENTIRETY
5) TEMPERATURE AND PRESSURE RELIEF DRAIN PIPING TO TERMINATE AT 90 DEGREE DOWN ON EXTERIOR WITH NO THREADED END
6) PROVIDE APPROVED GAS SHUT OFF VALVES AT APPLIANCES