Permit: T09PL01406

Parcel: 126210710

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T09PL01406

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/26/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
1) HOUSE SYSTEM ONLY
08/24/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE TEST ON ENTIRE GAS SYSTEM, TEST THRU ALL IN LINE VALVES UP TO ALL APPLIANCE SHUT OFF VALVES INTO HEARTH OF FIREPLACES
2) SECURE GAS PIPING TO FURNACE AT GUEST HOUSE AND PROVIDE FASTENERS AT ALL VENT PIPING JOINTS. NOTE: SINGLE WALL VENT CONNECTOR REQUIRE 6" CLEARANCE FROM COMBUSTIBLES (DRPAES) CURTINS
3) PROVIDE AN AGA OR CSA APPROVED GAS SHUT OFF VALVE AT STOVE
4) TEST MUST BE THRU LOG LIGHTER VALVES INTO HEARTH OF FIREPLACES (3)
5) HAVE CITY APPROVED GAS ISOMETRIC ON SITE
6) POOL HEATER REQUIRED A ASME PRESSURE RELIEF DEVICE THAT MEETS OR EXCEEDS BTU RATING OF POOL HEATER
7) MAKE THE GAS SYSTEM (1) SYSTEM AND TEST IN IT'S ENTIRETY
8) PROVIDE SUPPORT AND SECURE GAS PIPING IN BASEMENT TO STOVE