Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/24/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
1) GAS CARD AT METER
08/18/2009 PLUMBING - FINAL Cancelled CANCELLED PER CONTRACTOR EDWARD #304-8888
08/18/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL GAS PIPING AND PROVIDE MINIMUM 10 PSI TEST WITH TESG GAUGE IN 1/10 POUND INCREMENTS AT TIME OF INSPECTION HOLDING TEST WITH NO LOSS OF PRESSURE
2) PROVIDE APPROVED VENTING SYTEM FOR WATER HEATING
3) PROVIDE RIDGID NIPPLE THRU WATER HEATER ENCLOSURE FOR GAS PIPING
4) PROVIDE TEMPERATURE AND PRESSURE RELIEF DRAIN PIPING TERMINATING 6"-24" FROM FINISH GRADE OF APPROVED MATERIAL
5) PROVIDE ACCESS TO ROOF TOP UNIT FOR INSPECTION
6) PROVIDE APPROVED GAS SHUT OFF VALVES AT ALL APPLIANCES
7) GAS FLEXES CANNOT PASS THRU PARTITIONS-PROVIDE RIDGID PIPING
8) LIST NOT COMPLETE