Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09PL01363
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/23/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) OK FOR GAS 2) UCC'S LEFT AT METER |
|
08/17/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) FLEX CONNECTOR MAY NOT PASS THRU WALL OR PARTITION 131, 133 T & P RELIEF MAY NOT DSCHARGE UNDER HOUSE 2) VERTICAL PIPING TO BE SUPPORTED 3) UNDER HOUSE PIPING NOT SUPPORTED PER 2006 UPC 4) PROVIDE ACCESS TO FURNACE |
|
08/12/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) GAS PIPING SHALL NOT BE INSTALLED IN OR ON THE GROUND UNDER ANY BLDG, BUT SHALL BE KEPT AT LEAST 6" ABOVE GRADE 2) UNIONS MAY NOT BE INSTALLED AT INACCESSIBLE LOCATIONS. NOT INSTALLED PER PLAN 3) ALL PIPING TO BE SUPPORTED PER 2006 UPC 4) WATER HEATER AND FURNACE REQUIRE SEDIMENT TRAPS 5) WATER HEATER REQUIRES T & P RELIEF DRAIN 6) UNABLE TO ENTER #131 |