Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 08/11/2009 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) WATER LINE-OK 2) GROUNDING-OK (OK TO COVER) 3) THE NEW VACUUM BREAKER IS NOT THE CORRECT BACKFLOW PROTECTION WHEN THERE IS A VALVE DOWNSTREAM OF THE VACUUM BREAKER ON THE LANDSCAPING WATER SUPPLY SYSTEM. EITHER PROVIDE CORRECT BACKFLOW PROTECTION DEVICE OR REMOVE VALVE IN VALVE BOX 2) NOTE: AN ELECTRIC VALVE COULD BE INSERTED IN THE VACUUM BREAKER DEVICE IF THE DOWN STREAM VALVE IS REMOVED |
|
| 08/10/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) GROUNDING CLAMP TO BE CONNECTED TO COPPER PIPE NOT TAPED AREA 2) CONNECTION OF BROKEN GROUND WIRE TO BE IRREVERSIBLE CRIMP OR EXOTHERMIC WELD 3) PROVIDE 10' IN GROUND COPPER PIPING FOR GROUNDING SYSTEM |