Permit: T09PL01343

Parcel: 134170520


Addresses:

7409 E PRINCETON DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/13/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
08/11/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) WATER LINE-OK
2) GROUNDING-OK (OK TO COVER)
3) THE NEW VACUUM BREAKER IS NOT THE CORRECT BACKFLOW PROTECTION WHEN THERE IS A VALVE DOWNSTREAM OF THE VACUUM BREAKER ON THE LANDSCAPING WATER SUPPLY SYSTEM. EITHER PROVIDE CORRECT BACKFLOW PROTECTION DEVICE OR REMOVE VALVE IN VALVE BOX
2) NOTE: AN ELECTRIC VALVE COULD BE INSERTED IN THE VACUUM BREAKER DEVICE IF THE DOWN STREAM VALVE IS REMOVED
08/10/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) GROUNDING CLAMP TO BE CONNECTED TO COPPER PIPE NOT TAPED AREA
2) CONNECTION OF BROKEN GROUND WIRE TO BE IRREVERSIBLE CRIMP OR EXOTHERMIC WELD
3) PROVIDE 10' IN GROUND COPPER PIPING FOR GROUNDING SYSTEM