Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 07/17/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/07/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) 10 PSI TEST REQUIRED ON SYSTEM 2) NEW WATER HEATER REQUIRES A PERMIT AND THE FOLLOWING CORRECTIONS: T & P MAY NOT REDUCE IN SIZE WATER FLEXES ARE KINKED SEDIMENT TRAP REQUIRED IN ACCESSIBLE LOCATION BUSHINGS MAY NOT BE CONCEALED PROPER SLOPE ON VENT CONNECTOR AND PROPER TEE FITTING AT COMMON VENT REMOVE ALL TAPE AND CORRECT ALL JOINTS SECURE WITH GALV SCREWS GALVANIZED FITTINGS NOT ALLOWED ON COPPER SYSTEM COMBUSTION AIR REQUIRED FLEX TO FURNACE IS TOO SMALL FOR 75000 BTU SEAL WALL PENETRATIONS ELECTRICAL BONDING REQUIRED |