Permit: T09PL01115

Parcel: 12106260A


Addresses:

1632 N VAN BUREN AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/09/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
07/07/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) TEST OK
2) PROVIDE TYPE B CAP ON VENT, SECURE TO DRAFT COLLAR
3) INSTALL AGA VALVES
4) SECURE PIPE AT WALL
5) SWEAT ALL ON T & P TERMINATION
07/02/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
07/01/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) WORK NOT COMPLETE
2) 10 PSI TEST REQUIRED
3) YELLOW TRACER WIRE REQUIRED IN NON METALLIC YARD PIPING
4) REQUIRE LISTED PIPE FITTINGS, THREAD PROTECTORS MAY NOT BE USED
5) FLASHINGS AT ROOF PENETRATION
6) WATER HEATER REQUIRES CORRECTIONS AT VENT TERMINATION AND T & P
7) SUPPORT AND SECURE ALL PIPING