Permit: T09PL01112

Parcel: 126133040


Addresses:

4534 E 17TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/07/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
07/02/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) UNIT #4536-OK
2) UNIT #4534 REQUIRES TEST TO HOLD WITH NO LOSS OF PRESSURE
07/01/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEE NOTES ON 4534 E. 17TH ST
2) TEST ON UNIT 4536-OK
4534 E. 17TH ST:
1) PROVIDE BONDING OF BLDG GAS PIPING
2) SEAL PIPE ENTRY INTO BLDG
3) PROVIDE CORRECT VENT SYSTEM WITH APPROVED MATERIALS FOR WATER TEST AND FURNACE
4) PROVIDE RIGID NIPPLE THRU FURNACE HOUSEING
5) PROVIDE FULL SIZE WATER HEATER TEMPERATURE AND PRESSURE RELIEF DRAIN PIPING OF APPROVED MATERIALS TERMINATING 6" TO 24" AFF
6) MAKE SURE TEMPERTURE AND PRESSURE RELIEF ARE FUNCIONAL FOR WATER HEATERS