Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) GAS CARD AT METER |
|
| 06/29/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) T.V. IS ON 2) NO ANSWER AT DOOR, TRIED FOR 10 MINUTES 3) NO ACCESS |
|
| 06/25/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES ABOVE, COMPLETE THESE NOTES AND COMPLY OR YOU WILL BE ISSUED A REINSPECTION FEE. |
|
| 06/19/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TEST TO BE ON ENTIRE GAS SYSTEM TO APPLIANCES 2) PROVIDE A PRE-FABRICATED RISER AT BLDG OR FACTORY COATED PIPING, WITH TOOL MARKS AND FITTINGS PRIMED THEN TAPED 3) ROUTE GAS PIPING TO WATER HEATER SO IT CAN BE REMOVED WITHOUT REMOVING GAS PIPING 4) PROVIDE BONDING OF GAS PIPING 5) PROVIDE APPROVED VENT THRU ROOF WITH APPROVED VENT TERMINATION AT VENT CAP |