Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09PL01033
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/16/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOND WIRE TO BE GAS PIPE TO COLD WATER SIDE IF USED PROVIDE A #4 OR #6 SOLID WIRE (COPPER) FOR BONDING 2. SEAL PIPE PENETRATIONS INTO BLD. FOR WATER HEATER AREA 3. PROPERLY SECURE GAS DROP AT FURNACE 4. APPLY MASTIC TO PIPE SUPPORTS ON ROOF TO HOLD PIPING IN PLACE 5. VENT FROM FURNACE TO BE EXTENDED TO 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE WITH FULL SIZE APPROVED DOUBLE WALL VENT PIPING (MAKE CORRECTIONS RECALL 03090 INSPECTION) |