Permit: T09PL01033

Parcel: 129023490


Addresses:

2633 E ARROYO CHICO


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T09PL01033

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/18/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
06/16/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOND WIRE TO BE GAS PIPE TO COLD WATER SIDE IF USED
PROVIDE A #4 OR #6 SOLID WIRE (COPPER) FOR BONDING
2. SEAL PIPE PENETRATIONS INTO BLD. FOR WATER HEATER AREA
3. PROPERLY SECURE GAS DROP AT FURNACE
4. APPLY MASTIC TO PIPE SUPPORTS ON ROOF TO HOLD PIPING IN PLACE
5. VENT FROM FURNACE TO BE EXTENDED TO 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE WITH FULL SIZE APPROVED DOUBLE WALL VENT PIPING
(MAKE CORRECTIONS RECALL 03090 INSPECTION)