Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
Permit Number - T09PL00956
Inspection Description - PLUMBING - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/24/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. ADD SUPPORT ON PIPING AT STOVE 2. MAKE ROOF JACK WATER TIGHT 3. SEAL HOLE THRU WALL ON OUTSIDE 4. RUN PIPING FOR T&P AT WATER HEATER 6" TO 24" OFF OF GROUND WITH APPROVED PIPING (CPVC) OR APPROVED PIPING |
|
06/23/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* NO ONE AT HOME - UNABLE TO DO INSPECTION 9:05 AM |