Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09PL00941

Parcel: 134148010

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T09PL00941

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/16/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
06/12/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PLEASE LEAVE A MESSAGE WITH A CONTACT PHONE NUMBER IF AN ADULT IS NOT GOING TO BE PRESENT ON DAY OF INSPECTION -- 1:26 NO ACCESS
06/11/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
06/08/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE 1" AIR GAP FROM LIP OF DRAIN PAN AND T&P DRAIN PIPING
2. REMOVE ALL TAPE AT JOINTS OF VENT PIPING ESPECIALLY AT DRAFT SPACE BETWEEN SINGLE WALL AND DOUBLE WALL CONNECTION
3. PROVIDE A NIPPLE WITH NO THREADS ON DISCHARGE END OR COPPER MALE ADAPTOR AT 125 POUND PRESSURE RELIEF DEVICE.