Permit: T09PL00901

Parcel: 111030650

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/08/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
06/05/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REPLACE GAS FLEX AT WATER HEATER
2. REMOVE COMBUSTIBLE DEBRIS FROM AROUND WATER HEATER, PROVIDE NON-COMBUSTIBLE BASE AT WATER HEATER
3. PROVIDE B-VENT WHERE WATER HEATER FLUE PIPING EXTENDS THROUGH CEILING
4. PROVIDE NEW GAS FLEX AT MAIN INLET TO STRUCTURE
5. WATER HEATER T&P PIPING TO BE A MIN. 3/4" AND TERMINATE BELOW TRAILER
6. 220V ROMEX TO DRYER MUST BE IN CONDUIT OR IN WALL
7. PROVIDE NEW GAS FLEX TO STOVE AND HEATER
8. PROVIDE GAS LINE PRESSURE TEST