Permit: T09PL00822

Parcel: 116125560

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
10/15/2009 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) CORRECTIONS MADE OK
2) OK FOR GAS
10/09/2009 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) PROVIDE PSI TEST MINIMUM OF 10 PSI
2) REMOVED TEE AT UDERGROUND AT WATER HEATER PAN
3) RUN T & P TO WATER HEATER 6" TO 24" OFF GROUND
4) PUT GROUND WIRE ON COLD WATER SIDE
09/28/2009 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) REQUIRE MINIMUM 10 POUND TEST
2) THREAD PROTECTORS ARE NOT APPROVED COUPLINGS
3) GAS PIPING MAY NOT RUN ALONG THE GROUND, BUT MUST BE AT LEAST 6" ABOVE GRADE
4) AT WATER HEATER: NO SEDIMENT TRAP, T & P RELIEF DRAIN NOT APPROVED (CHECK VALVE), WATER HEATER VENT NOT APPROVED, NOT TERMINATED PROPERLY
5) MUST BE ON AN APPROVED BASE