Permit: T09PL00716

Parcel: 10709066D

Inspection Status: Denied

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
04/30/2009 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VENT/FLUE NEED DBL WALL CONNECTED TO AMBER VENT THRU ROOF
2) NEED 10 POUND PRESSURE TO HOLD FOR MINIMUM 15 MINUTES
3) NEED WORKING T & P VALVE, WITH 3/4" DIAMETER LINE DOWN TO GRADE
4) NEED A SHUT OFF VALVE FOR COLD SIDE OF H20 SUPPLY
5) VALVE FLEX CONNECTION IS RUSTED
6) FURNACE/HEAT SOURCE REQUIRED FOR UNIT. GAS RUNS TO INSIDE OWNER CLAIMS NO GAS FURNACE
7) REMOVE PANEL ABOVE FURNACE TO VERIFY FLUE CONNECTION AND COMB/RELIEF AIR