Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/22/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 04/09/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT EXPANSION TANK 2. IF WATER HEATER IS ON ELEVATED PLATFORM SUBJECT TO DAMAGE A DRIP PAN IS REQUIRED 3. WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN PIPING SHALL GRAVITY DRAIN TO DAYLIGHT OR APPROVED RECEPTOR TERMINATING AT 90 DEG. DOWN PLEASE VERIFY AND PROVIDE POINT OF TERMINATION |