Permit: T09PL00529

Parcel: 130171860


Addresses:

4129 E 29TH ST #101

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/22/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
05/21/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR CANCELLED
05/20/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SEPARATE PERMIT HAS BEEN PULLED FOR ELECTRICAL - OK
2. SECURE SINKS, PROVIDE GRATES ON FLOOR SINKS
3. PROVIDE MIN. 1" AG AT SANITIZE COMP.
4. INSTALL FRANK PATTERN CO COVERS.
5. EXPOSE ALL CO's SHOWN ON PLAN
6. SEAL THREADS ON CLEANOUTS
7. RECIRCULATING HW SYSTEM REQUIRES INSULATION AND IS SPECIFIED ON PLAN
8. PROVIDE ACCESS TO HIGH CEILING AND ROOF
9. TRAP & TRAP ARM SHALL BE THE SAME SIZE
10. FOLLOW PIPING DETAIL AND NOTES
11. LIST MAY NOT BE COMPLETE.
05/19/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE ALL WORK
ALSO, SEE PREVIOUS INSP. HISTORY
PROVIDE CORRECT USE OF FITTINGS
CALL IN ALL INSP. ON ACTIVITY CARD