Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2009 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :* THE BOTTOM OF THE SEPTIC TANK NEEDS TO BE BROKEN SO THAT IT WILL NOT RETAIN WATER. PUMP SEWAGE OUT FIRST. BUILDING CONNECTIONS MADE OK OK TO COVER ALL AREAS BUT TANK ABS RISER IS NOT APPROVED METHOD OF SUPPORT FOR N/H |
|
| 03/30/2009 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* 1. UNDERGROUND PIPING CORRECTIONS MADE OK OK TO COVER 2. I NEED TO SEE ALL CONNECTIONS MADE TO EXISTING PIPING AT BLDG's 3. I NEED TO SEE SEPTIC TANK PUMPED AND SIDES OR BOTTOM BROKEN BEFORE FILLING 4. A VENT MUST RISE AT LEAST SIX INCHES ABOVE OVERFLOW OF FIXTURE BEFORE OFFSETTING HORIZONTALLY |
|
| 03/23/2009 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection :* 1. MUDDY TRENCHES AND WET SPOTS INDICATE LEAKS 2. ALL CHANGES TO THE PLAN MUST BE REDLINED PRIOR TO INSPECTION 3. ABS REQUIRES A MINIMUM OF 12" OF COVER AT ALL POINTS 4. ABS IS NOT PERMITTED IN EXPOSED EXTERIOR LOCATIONS 5. EXCEPT WHERE THE BLDG. DRAIN CONNECTS TO THE BLDG. SEWER, ALL UNDERGROUND FITTINGS ARE TO BE OPEN IN THE DIRECTION OF FLOW. |