Permit: T09PL00379

Parcel: 137060170

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
03/19/2009 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
03/03/2009 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) CANNOT RELEASE GAS UNTIL FURNACE IS CHECKED OUT BY MECHANICAL CONTRACTOR
2) APPROX 80' OF PIPE, (YARD) STARTS AT METER IN ALLEY AT 1" DIAMETER COMES OUT OF GROUND AT UNIT, AT 3/4" DIAMETER. WHAT IS BTU RATING OF FURNACE, UNABLE TO REMOVE COVER. VERIFY PIPE IS CORRECT SIZE TO HANDLE BTU LOAD
3) BTU LOAD ON LINE WOULD BE 65,000 FOR RANG ? FOR FURNACE
4) NUMEROUS ELECTRICAL PROBLEMS, POWER IS ON:
A) FEEDER FROM METER STRANDED AL. 1/2 OF WIRE CUT TO FIT INTO LUG CONNECTIONS
B) TWO SIZES OF FUSES IN DISCONNECT
C) CAN'T OPEN SUB PANEL SHELF IN THE WAY
D) NUMEROUS WIRES IN LUG CONNECTION AT UNIT DISCONNECT, ONLY ONE WIRE ALLOWED
E) #12 WIRE FEEDING H20 HTR ON OUTSIDE OF BLDG MISSING T & P LINE AND ENCLOSURE
F) SOME RE-WIRING BEING DONE AND ENCLOSING PORCH
G) CHECK FOR GROUND SYSTEM AT UNIT
H) FURNACE NOT TO BE OVER 35,000 BTU, IF LINE IS 3/4"