Permit: T09PL00371

Parcel: 10704006A


Addresses:

1560 W GRANT RD


Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Permit Number - T09PL00371

Inspection Description - PLUMBING - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
05/04/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
THERE IS A DIRECTLY CONNECTED COFFEE BREWER INSTALLED, PROVIDE CORRECT BACKFLOW PROTECTION FOR WATER SUPPLY OR PROOF OF 1" AIR GAP FOR WATER ENTRY TO FLOOD RIM OF COFFEE MAKER
04/24/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. CAN ONLY HAVE ONE SLIP NUT AFTER
TRAP ON 3-COMP. SINK
2. PROVIDE ALL FULL SIZE FITTINGS