Permit: T09PL00265

Parcel: 130121660


Addresses:

3745 E 33RD ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/25/2009 PLUMBING - FINAL Approved
02/17/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
TEST GAUGE IS DAMAGED AND FROZEN AT 13 PSI WITH NO PRESSURE IN THE SYSTEM. PLEASE REPLACE WITH TEST GAUGE IN 1/10 POUND INCREMENTS AND HAVE MINIMUM
10 PSI ON ENTIRE GAS SYSTEM AT TIME OF REINSPECTION WITH NO LOSS OF PRESSURE FOR 15 MINUTES