Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS RECONNECT
Permit Number - T09PL00189
Inspection Description - PLUMBING - GAS RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2009 | PLUMBING - GAS RECONNECT | Approved | ||
02/13/2009 | PLUMBING - GAS RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE FLUE PIPE FOR THE FURNACE IS BROKEN AND DISCONNECTED 2) NEEDS 1" MINIMUM CLEARANCE TO COMBUSTIBLE MATERIAL AT ROOF |
|
01/30/2009 | PLUMBING - GAS RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO INSTALL SEDIMENT TRAP ON GAS LINE AT W/HEATER 2) IS FURNACE IN ATTIC, GAS SUPPLIED-WILL NEED A LADDER TO ACCESS 3) WAS ENCLOSURE OF EXISTING PORCH-PERMITTED ? |