Permit: T09PL00183

Parcel: 118031950

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/04/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
PRESSURE TEST OK
OK TO COVER
OK FOR GAS
02/03/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. ALL NON-METALLIC UTILITIES SHALL BE TRACEABLE
GAS P.E. PIPING TO HAVE YELLOW TRACER WIRE
H.B. 2256 - 1211.1.7 SECTION "C" (14 GAUGE)
2. 1211.10.3 2006 UPC REQUIRE EXTERIOR SHUT OFF VALVE
3. 1211.14 ELECTRICAL BONDING - BOND BETWEEN WATER AND GAS (#6)
4. 1212.7 SEDIMENT TRAP (NOT REQUIRED)
5. 1211.2.1 PROTECTED PIPE
6. A FACTORY BENT SINGLE PIECE RISER, OR 30" HORIZONTAL SECTION REQUIRED BEFORE TRANSITION TO P.E
7. REMOVE TAPE AT DBL WALL VENT
8. INSTALL APPROVED GAS VALVE AT WATER HEATER
9. REQUIRE CLEANFILL FOR BACKFILL
10. EXTEND T&P RELIEF