Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09PL00182
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/03/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
01/30/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PAPERWORK FOUND |
|
01/29/2009 | PLUMBING - FINAL | Cancelled | CANCELLED PER SELMA OF DEANS PLUMBING #575-0190 | |
01/29/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE PIPING AT 2ND WATER HEATER & WASHER BOX PROVIDE WATER HAMMER ARRESTORS ON WASHER SUPPLY PIPING. EXPOSE YARD WATER PIPING FROM METER TO HOUSE AND REPAIR LEAK ON OWNER SIDE OR CONTACT C.O.T WATER IF ON CITY SIDE OF METER. 2. BREAK OFF TAMPER SCREWS ON VACUUM BREAKERS AT HOSE BIBS 3. INSULATE PIPING SUBJECT TO FREEZING 4. PROVIDE SEPARATION OF HOT & COLD TUBING 5. SUPPORT ALL PIPING AT CORRECT INTERVALS AND AT ANGLE STOPS WITH APPROVED METHODS AND DEVICES 6. PROPERLY SECURE & SUPPORT SHOWER VALVE 7. PIPING TO USE FITTINGS FOR CHANGES OF DIRECTION ON ROOF 8. PIPING TO BE PROPERLY SUPPORTED ON ROOF 9. PROVIDE ROOF JACKS AT ALL ROOF PENETRATIONS 10. PROVIDE FHA STRAPS OR NAIL PROTECTION PLATES WHERE REQUIRED 11. SECURE PIPING (HOT & COLD) AT WATER HEATER 12. INSTALL VENT TO DRAFT HOOD OF WATER HEATER |