Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09PL00056
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/09/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* GAS CARD @ METER SW GAS 889-1888 |
|
02/02/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT PIPING ON ROOF AT CHANGES OF DIRECTION, AND CORRECT INTERVALS FOR SIZING WITH WEATHERPROOF SUPPORTS AND SECURE PROPERLY 2. OPEN VALVE AT NORTHEAST UNIT, OR REMOVE IT AND TEST TO APPROVED APPLIANCE SHUT OFF VALVE 3. PROVIDE MINIMUM TEST PER NOTE #1, 2, 3 FROM 1/14/09 WITH FUNCTIONAL TEST GAUGE (GAUGE IS DAMAGED) |
|
01/15/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
01/14/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. TEST TO BE IN PLACE, MINIMUM 10 PSI ON ENTIRE GAS SYSTEM, TEST GAUGE TO BE IN 1/10 POUND INCREMENTS 2. PLEASE PROVIDE ACCESS TO ALL GAS APPLIANCES FOR SAFETY INSPECTION 3. TEST TO HOLD FOR MINIMUM 15 MINUTES WHILE INSPECTION IS ONGOING |