Permit: T09PL00056

Parcel: 12517032A


Addresses:

3805 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T09PL00056

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/09/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
GAS CARD @ METER
SW GAS 889-1888
02/02/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT PIPING ON ROOF AT CHANGES OF DIRECTION, AND CORRECT INTERVALS FOR SIZING WITH WEATHERPROOF SUPPORTS AND SECURE PROPERLY
2. OPEN VALVE AT NORTHEAST UNIT, OR REMOVE IT AND TEST TO APPROVED APPLIANCE SHUT OFF VALVE
3. PROVIDE MINIMUM TEST PER NOTE #1, 2, 3 FROM 1/14/09 WITH FUNCTIONAL TEST GAUGE (GAUGE IS DAMAGED)
01/15/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
01/14/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. TEST TO BE IN PLACE, MINIMUM 10 PSI ON ENTIRE GAS SYSTEM, TEST GAUGE TO BE IN 1/10 POUND INCREMENTS
2. PLEASE PROVIDE ACCESS TO ALL GAS APPLIANCES FOR SAFETY INSPECTION
3. TEST TO HOLD FOR MINIMUM 15 MINUTES WHILE INSPECTION IS ONGOING