Permit: T09PL00016

Parcel: 136373770


Addresses:

3847 S PALM SIDE DR

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
01/26/2009 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection :*
01/16/2009 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLAN SHOWS 3/4 TO FURNACE-ACTUAL CHANGES TO 1/2" AT LAUNDRY ROOM
2) NEED OPERABLE TEST GAUGE
3) NEED PERMIT FOR FURNACE CHANGE
4) B-VENT CANNOT BE RUN AT LESS THAN 30 DEGREE SLOPE
5) CHANGE PIPE TO 3/4 OR UPDATE PLAN AND HAVE APPROVED