Permit: T09OT02772

Parcel: 13323193C


Addresses:

750 N KOLB RD


Inspection Status: Denied

Inspection History: FIRE - FINAL

Permit Number - T09OT02772

Inspection Description - FIRE - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
12/29/2009 FIRE - FINAL Denied Not approved 12/19/09
1.) Where panic hardware is provide, it shall be the only locking device for that door. Must remove the thumb-turn lock from the main doors.( main door, rear exit door kitchen area)
2.) Need current annual Fire Alarm inspection report.
3.) Openings in walls and ceilings must be covered.
4.) Remove material stored on top of ceiling tile over walk-in cooler next to SE exit, kitchen area.
5.) All exit signs are burnt out.
6.) SE exit door in kitchen area sticks. Hard to open.
7.) Need semi-annual inspection report for hood exhaust system.
8.) Need a "K" type portable fire extinghuisher for kicthen area.
9.) Door for the electrical room must be labled. "ELECTRICAL".
10.) Secure wire in the electrical conduit runnining down fron ceiling. (kitchen area)
11.) Portable fire extinghuisher cabinets must be provided with extinghuishers.
12.) NW exit (main floor) must be readily openible at all times. Remove temporary security barrier from door.
13.) Replace broken glass on NW door.
14.) All emergency back-up lights are burnt out.